// Chapter 22.4 · PLC · Timers & Counters
Timers and Counters to IEC 61131-3: TON, TOF, TP, CTU, CTD and CTUD with Timing Diagrams and Real-World Examples
Timers and counters are the main reason a PLC pays for itself against a relay panel. One timer in the program replaces a physical timer relay costing tens of dollars, and its time can be set precisely from the HMI. This page uses the names from IEC 61131-3, which is the template for the instructions of every brand.
- TON: IN must stay on for the full PT before Q = 1 · TOF: Q stays on for PT after IN goes off · TP: one pulse of length PT per rising edge
- CTU counts rising edges of CU · Q = 1 when CV ≥ PV · R clears it
- Accuracy ≈ ± one scan time
- Very long times: use a minute timer feeding a counter
The three timer types Basic
T1 TON — on-delay
T2 TOF — off-delay
T3 TP — fixed-length pulse
T4 Software timer accuracy
A conveyor that sounds a horn for 5 s before starting, with a cooling fan that runs on for 2 minutes after it stops
Run command M0.0 (seal-in from START/STOP) ·
T1 = TON(M0.0, 5s)Horn:
Q0.1 = M0.0 & !T1· conveyor:Q0.0 = T1(runs once the 5 s are up)Fan:
T2 = TOF(Q0.0, 120s)·Q0.2 = T2— runs together with the conveyor and stays on for another 2 minutes after the conveyor stops
T5 Flasher from two timers
Counters Basic
T6 CTU — up counter
T7 CTD — down counter
CTUD combines both in one block (QU and QD). Use it to count how many items are inside an area, such as cars entering and leaving a car park, or parts in a buffer between two machines.
A filter change every 500 running hours, but the maximum timer PT is 24 h
Create a pulse every hour while the pump runs:
T1 = TON(Q0.0 & !T1, 3600s)(resets itself when done)Count the pulses:
C1 = CTU(T1, I0.5, 500)· I0.5 = reset button pressed after changing the filterWarning:
Q0.3 = C1· make C1 retentive so its value is not lost in a power failure
Names in each brand
| IEC 61131-3 | Siemens S7-1200/1500 | Mitsubishi FX5/iQ | Omron CP/NX |
|---|---|---|---|
| TON | TON (IEC_TIMER) | OUT T0 K50 (100 ms) / TON FB | TIM / TON |
| TOF | TOF | TOF FB (or a circuit) | TOF |
| TP | TP | TP FB | TP |
| CTU | CTU | OUT C0 K10 / CTU FB | CNT / CTU |
Older timers in some brands are set as a number of “time-base” units, e.g. K50 on a 100 ms base = 5 s. Always check the time base when moving a program between models.
High-speed counters Intermediate
A CTU in the program can count at no more than about half the scan rate (it must see 0 for one scan and 1 for one scan). For example, a 10 ms scan counts no faster than ~50 Hz, and the input filter time must be subtracted too. Encoders and high-speed sensors must be wired to the CPU's high-speed counter (HSC) inputs, which count in hardware at tens or hundreds of kHz and support two-phase A/B signals.
T8 Software counter limit
Frequently asked questions
How accurate is a PLC timer?
A timer is updated when it is executed in each scan, so its error is about one scan time (plus the resolution of its time base, e.g. 1 ms, 10 ms or 100 ms). That is fine for general work, but if you need millisecond accuracy use a hardware timer, a cyclic-interrupt task or the CPU's pulse outputs.
A timer stops timing when it is in a part of the program that is not called. What is happening?
A software timer only times while its instruction is being executed. If it sits inside a function or a jumped-over section that is not running, it stops timing or freezes its value. Call the timer every scan and control it through its IN input instead.