// Chapter 22.6 · PLC · Motor Control with a PLC
Motor Control with a PLC: DOL, Reversing, Star–Delta, I/O Lists, Wiring, Hard-Wired Interlocks and Contactor Feedback Monitoring
Moving the logic from a relay panel into a PLC gains flexibility, status display and fault detection — but the safety of the original circuit must not be lost. This page draws a clear line between what lives in software and what must stay in hardware, and gives working programs for all three motor circuits.
- Keep in hardware: emergency stop via a safety relay · overload 95-96 · NC + mechanical interlocks
- The PLC does: self-holding, sequencing, timers, feedback checks, alarms, run-hour counting
- Feedback:
- Star–delta: Y first → K1 → time elapsed → Y drops out → dead time → Δ
Dividing the jobs: hardware vs software Basic
| Function | Where | Why |
|---|---|---|
| Emergency stop | Safety relay / safety PLC cuts coil power + PLC reads the status | Must work even if the standard PLC fails or its program is edited |
| Overload | 95-96 in series with the coil + 97-98 into the PLC | Trips even if the PLC hangs, and the cause can be displayed |
| Short-circuit interlock | Auxiliary NC + mechanical + in the program | A shorted transistor output or a forced bit must not cause a short circuit |
| Self-holding, sequencing, timers | Program | Easy to change, settable from the HMI |
| Detecting a welded / non-pulling contactor | Program + feedback contacts | Only possible when there is a controller with logic |
DOL with a PLC and feedback checking Basic
| Address | Device | Type |
|---|---|---|
| I0.0 | -S0 STOP | NC (1 = healthy) |
| I0.1 | -S1 START | NO |
| I0.2 | -F2 97-98 or auxiliary 95-96 | NC (1 = healthy) |
| I0.3 | -K1 13-14 feedback | NO |
| Q0.0 | -K1 coil (via 95-96) | Relay or interposing relay |
| Q0.1 / Q0.2 | Run lamp / fault lamp | — |
M1 Run command
M2 Feedback discrepancy
What M2 catches: commanded but not pulled in (blown coil fuse, open coil, 95-96 open) and not commanded but still pulled in (welded contacts, stuck output). The second case is dangerous: raise an alarm and disconnect with the upstream device.
Reversing with a PLC Intermediate
M3 Software interlock
Adding of the other direction (feedback from the real contactor) stops the program commanding the new direction until the old contactor has actually dropped out. A reversal delay timer of 0.5–2 s is also commonly added to let the motor slow down.
Star–delta with a PLC Intermediate
M4 Star–delta sequence
(* Structured Text: star–delta with feedback check *) Run := (PB_Start OR Run) AND PB_Stop_NC AND OL_NC AND NOT Fault; TY(IN := Run, PT := T#6S); // star period KY := Run AND NOT TY.Q AND NOT KD; // K2 star K1 := Run AND (FB_Y OR K1); // K1 after star has really pulled in TDead(IN := TY.Q AND NOT FB_Y, PT := T#80MS); // wait for K2 to really drop out, then time the dead band KD := Run AND TDead.Q; // K3 delta TChk(IN := (K1 XOR FB_1) OR (KY XOR FB_Y) OR (KD XOR FB_D), PT := T#1S); IF TChk.Q OR (FB_Y AND FB_D) THEN Fault := TRUE; END_IF
Note: the dead time starts when the feedback from K2 confirms it has dropped out, not when it is commanded off — this protects against a welded K2 contact. A plain relay circuit cannot do this. The simulator below is a simplified version without feedback.
Test the sequence in the simulator and answer the questions
Press START: record the order in which Q0.1 (Y) and Q0.0 (K1) turn on — why must Q0.1 come on first? (So the star point is made before the windings are energised.)
Watch the ET bars of T1 and T2: how long is Q0.1 off while Q0.2 is not yet on? (80 ms = the PT of T2.)
Edit the Q0.1 rung to remove the
!Q0.2condition and reload. Does the system still work, and why should this interlock stay anyway?
Frequently asked questions
With a PLC, do I still need auxiliary-contact interlocks in the coil circuit?
Yes. The interlocks that prevent short circuits (K1/K2 for reversing, K2/K3 for star–delta) must work even if the PLC fails, a transistor output shorts on, or someone forces a bit. An NC contact of the opposing contactor in series with each coil, plus a mechanical interlock, is still required. The program is an additional layer, not the only one.
Can I wire the overload relay only to the PLC?
Technically yes, but good practice is to put 95-96 in series with the contactor coil directly (so it trips even if the PLC hangs) and bring 97-98 or an auxiliary contact into the PLC for status display and event logging.