  4. Soft starters · Autotransformers

// Chapter 21.10 · AC Motor Control · Soft Starters & Autotransformers

Soft Starters, Autotransformers and Motor Starting Methods Compared: Current, Torque, Voltage Dip and Cost

Every method that lowers the voltage at start-up obeys the same rule: current falls in proportion to voltage, but torque falls with the square of voltage. This page uses that rule to compare starting methods with numbers, and explains the soft starter, now a favourite choice for modern pump installations.

By Ajarn ModUpdated
In 30 seconds
  • Reduce the voltage by a factor kk → current × kk, torque × k2k^2
  • Soft starter: thyristors chop the waveform, ramp the voltage, limit current to 2–4 In, then bypass
  • Autotransformer at tap aa: motor current × aa, line current × a2a^2, torque × a2a^2
  • Soft stop reduces water hammer in pump pipework — something star–delta cannot do

The rule of reduced-voltage starting Intermediate

T1 Reduced-voltage starting

VVn=k  ⇒  Ist=k Ist,DOLTst=k2 Tst,DOL\frac{V}{V_n} = k \;\Rightarrow\; I_{st} = k\,I_{st,DOL} \qquad T_{st} = k^2\,T_{st,DOL}

T2 Torque at a current limit

Tst=Tst,DOL(IlimIst,DOL)2T_{st} = T_{st,DOL}\left(\frac{I_{lim}}{I_{st,DOL}}\right)^2
Example T-1

Motor with Ia/In = 6.5, Ta/Tn = 2.2, current limit set to 3 In

  1. k=3/6.5=0.46k = 3/6.5 = 0.46 → initial voltage about 46 %

  2. T2: Tst=2.2(0.46)2=0.47T_{st} = 2.2(0.46)^2 = 0.47 Tn — enough for a centrifugal pump (~0.15 Tn) but not for a loaded conveyor (~1.0–1.5 Tn)

  3. Compare star–delta: current 6.5/3=2.26.5/3 = 2.2 In but torque 2.2/3=0.732.2/3 = 0.73 Tn — lower current yet higher torque, because the winding voltage falls only by 1/31/\sqrt3 while the line current falls to 1/3 (it behaves like an autotransformer with a=0.58a = 0.58, see Example T-2)

How a soft starter works Intermediate

Each phase has two thyristors (SCRs) connected in anti-parallel. The controller fires the thyristors at an angle α after the voltage zero crossing, so the motor receives only the tail end of each half-cycle. As α is steadily reduced, the rms voltage at the motor steadily rises. When full voltage is reached an internal bypass contactor closes and the thyristors stop conducting, so there is no heat loss in them during normal running.

-101020406080100120Time (ms) — the real 5–20 s ramp compressed to show the waveformα ≈ 140°α ≈ 70°α = 0 → bypassRMS voltage ramps up · frequency stays 50 Hz, so there is no extra torque — suits light-starting loads such as pumps and fans
Figure 1 · Motor voltage waveform during the ramp: from narrow slices of the wave (large α) to the full wave, then bypass

T3 RMS voltage vs firing angle (resistive approximation)

VrmsV=1−απ+sin⁡2α2π\frac{V_{rms}}{V} = \sqrt{1 - \frac{\alpha}{\pi} + \frac{\sin 2\alpha}{2\pi}}

Formula T3 applies to a resistive load and is meant to show the trend. A motor is an inductive load whose current lags, so the conduction interval is longer than this. A real soft starter measures the current and adjusts α by feedback.

Common starting modes

  • Voltage ramp: starts at an initial voltage (30–60 %) and rises linearly over a set time (5–30 s)
  • Current limit: adjusts the voltage so the current never exceeds k·In (2–4 In) throughout acceleration
  • Torque control: makes the torque rise smoothly so speed rises almost linearly; well suited to pumps and conveyors
  • Kick start: applies a short burst of high voltage at the start to overcome static friction
  • Soft stop / pump stop: lowers the voltage slowly when stopping so the water in the pipe decelerates without slamming the check valve (water hammer)

Connection and precautions

  • Upstream short-circuit protection is required: a circuit-breaker for Type 1 or semiconductor fuses for Type 2 coordination, per the manufacturer's tables
  • Never connect power-factor correction capacitors between the soft starter and the motor — connect them on the supply side and switch them out during the ramp
  • Set the motor rated current, overload class and number of starts per hour as specified by the manufacturer (the thyristors heat up during starting)
  • A line-side contactor or disconnect switch is needed for isolation during maintenance (blocked thyristors do not count as isolation)

Autotransformer starting Advanced

A three-phase autotransformer has taps such as 50 %, 65 % and 80 %. The motor receives aVaV and the motor current falls by a factor aa, but because the transformer also transforms current, the current in the supply lines falls by a2a^2 — a better reduction in line current than a resistor starter or a soft starter at the same torque. It is used for large motors such as raw-water pumps and large compressors (often built as a Korndorfer starter with closed-transition changeover).

T4 Autotransformer starter at tap aa

Imotor=a Ist,DOLIline=a2 Ist,DOLTst=a2 Tst,DOLI_{motor} = a\,I_{st,DOL} \qquad I_{line} = a^2\,I_{st,DOL} \qquad T_{st} = a^2\,T_{st,DOL}
Example T-2

65 % tap with a motor of Ia/In = 7, Ta/Tn = 2.3

  1. a2=0.4225a^2 = 0.4225 → line current 0.4225×7=2.960.4225 \times 7 = 2.96 In · torque 0.4225×2.3=0.970.4225 \times 2.3 = 0.97 Tn

  2. Compare a soft starter at the same line current of 2.96 In: T2 → only 2.3(2.96/7)2=0.412.3(2.96/7)^2 = 0.41 Tn

  3. The autotransformer gives almost twice the torque at the same line current, at the price of size, weight and cost

Comparing every method Intermediate

0×2×4×6×8×6.52.15DOL2.20.72Star–delta2.80.91Autotransf. 65 %3.00.45Soft starter 3·In1.51.50VFDLine current / InTorque / TnTorque falls with the square of voltage (T ∝ V²) — every reduced-voltage method trades torque for current, except the VFD
Figure 2 · Starting current and torque of an example motor (Ia/In 6.5 · Ta/Tn 2.15)

T5 Supply dip for any method

ΔU%≈3 VL Iline,stStr/uk+3 VL Iline,st×100\Delta U\% \approx \frac{\sqrt3\,V_L\,I_{line,st}}{S_{tr}/u_k + \sqrt3\,V_L\,I_{line,st}}\times 100
CriterionDOLStar–deltaAutotransformerSoft starterVFD
Line current6–8 In2–2.7 In2–4 In2–4 In≤ 1.5 In
Starting torqueHighest1/3a²(I/Is)²High, controllable
SmoothnessJerkTwo jerksModerateSmoothSmoothest
Soft stop✗✗✗✓✓ (controlled)
Cables to motor3633 (inside delta: 6)3, shielded
Harmonics———During ramp onlyContinuous
Relative cost11.5–23–52–33–6

Frequently asked questions

Can a soft starter control speed?

No. A soft starter reduces the voltage but the frequency stays at 50 Hz, so under normal load the motor always runs close to rated speed. Reducing the voltage under load only raises the slip and heats the motor. If you need speed control you must use a variable-frequency drive (VFD).

What is an inside-delta soft starter connection?

Some models place the thyristors in series with each winding inside the delta, so they carry only 0.58 In and a smaller soft starter can be used. However, six cables must be run to the motor, as with star–delta, and the connection must follow the manufacturer's diagram exactly.

Ajarn Mod · Teerawut Savangboon