// Research article · 3-phase motors

How Many Seconds Should a Star–Delta Timer Be Set To? Numerical Experiments on a Squirrel-Cage Induction Motor: Changeover Time, Dead Time, Current and Energy

“Five seconds is enough.” “Fans need fifteen.” “Pumps use eight.” Most star–delta (wye–delta) timer settings on site come from habit. This article is written as a research report: it asks the questions, builds a dynamic model of a squirrel-cage induction motor, verifies it, runs 14 sets of numerical experiments and turns the results into a formula and a table you can use, with case studies and a look at the future.

By Ajarn ModUpdated
In 30 seconds
  • Set the timer to tset=c τmt_{set} = c\,\tau_m with τm=Jωs/Tn\tau_m = J\omega_s/T_n and c ≈ 2–4 (pump 2.6 · fan 2.9 · constant torque at 50 % 3.7)
  • 37 kW pump ≈ 1.5 s (set 2–3 s) · high-inertia 7.5 kW fan ≈ 21 s
  • The changeover peak of pumps and fans ≈ DOL for any timer — a correct timer cuts the “high-current time” from ~1 s to ~0.05 s
  • Use the shortest safe dead time, wire KM3 in the lagging order, or use closed transition (peak 2.9–6.7·In)

Abstract — The changeover time of star–delta motor starters is usually set by experience, which leads to early changeovers, current surges, breaker trips and accumulated heating. This work simulates star–delta starting of a 7.5 kW 400 V 50 Hz double-cage induction motor with a space-vector dynamic model verified against the equivalent circuit (error 10⁻¹⁶) and a reference solver (error < 0.3 %), with pump, fan and conveyor loads. The results show that the right timer setting can be written as c τmc\,\tau_m with c ≈ 2–4, almost independent of motor size. The open-transition changeover peak of pumps and fans is 0.85–1.2 times the direct-on-line peak whatever the timer setting, but a correct timer shortens the high-current time about twenty-fold. The peak can be predicted from the vector difference between the delta voltage and the residual voltage. The lagging KM3 order, a short dead time and closed transition reduce it by 10–70 %. Star–delta cuts the supply I²t by 25–50 % but increases rotor heating by 30–55 %.

Keywords: star–delta, wye–delta, timer, mechanical time constant, residual voltage, dead time, closed transition, squirrel-cage motor

1. Introduction

Star–delta is the most widely used way to reduce starting current in Thailand and the region, because it needs only three contactors and a timer. In star the winding gets 1/31/\sqrt3 of the voltage, so current and torque fall to 1/3; when the motor is near full speed it is switched to delta (circuit and devices in Star–delta starter in detail). A question that looks simple still has no clear numerical answer: how many seconds should the timer be set to? Most manuals only say “when the speed reaches 85–90 %”, which an electrician cannot measure directly.

This work asks four research questions: (RQ1) how can the timer setting be found from catalogue data; (RQ2) what sets the current and torque peak at the changeover, and how much do the timer, the dead time and the phase order matter; (RQ3) what does star–delta really reduce in terms of current, energy and heat; (RQ4) what practical recommendations follow from the results?

2. Background

At the same speed, the star connection gives 1/3 of the delta line current and torque, and the breakdown torque also falls to 1/3. The motor can therefore accelerate only to its star equilibrium speed nYn_Y, where the star torque equals the load torque. The run-up time follows from Newton's second law for rotation:

t(ω1)=J∫0ω1dωTY(ω)−TL(ω)τm=J ωsTnt(\omega_1) = J\int_0^{\omega_1}\frac{d\omega}{T_Y(\omega) - T_L(\omega)} \qquad \tau_m = \frac{J\,\omega_s}{T_n}

The mechanical time constant τm\tau_m is the time rated torque would need to accelerate the rotating mass from rest to synchronous speed. With time measured in τm\tau_m and torque in TnT_n, the equation above contains no motor size at all, so the results carry over to other motors whose torque curves have a similar shape.

During the dead time, when the motor is disconnected, flux trapped in the rotor produces a residual voltage e‾\underline e at the terminals, which turns slower than the supply and drifts by an angle δ\delta. When KM3 closes, the transient is driven by the vector difference

δ≈sch ωstd+p TL2Jtd2∣ΔV‾∣=∣V‾Δ−e‾∣Ipk≈ka ∣ΔV‾∣VΔ ILR\delta \approx s_{ch}\,\omega_s t_d + \frac{p\,T_L}{2J}t_d^2 \qquad |\Delta\underline V| = |\underline V_\Delta - \underline e| \qquad I_{pk} \approx k_a\,\frac{|\Delta\underline V|}{V_\Delta}\,I_{LR}

where ka≈1.35–1.45k_a \approx 1.35\text{–}1.45 is the first-cycle asymmetry factor. The derivations and all formulas (E1–E24) are in Star–delta analysis, and the basics of torque–speed curves are in the induction motor lesson Induction motor.

3. Method

3.1 Model. A 7.5 kW 4-pole 400 V Δ 50 Hz motor with a double-cage rotor (In 14.0 A, Tn 49.3 N·m, 1471 rpm, Is/In 6.53, Ts/Tn 2.15, Tk/Tn 3.0, motor J 0.045 kg·m²), written as space-vector equations in physical winding quantities. The states are the flux linkages of the stator, the outer cage and the inner cage, plus the speed, solved with fourth-order Runge–Kutta every 0.1 ms. During the dead time the stator current is zero and only the two rotor cages are integrated (their flux is continuous across the switching).

3.2 Verification. Twelve steady-state points agree with the equivalent circuit to 10⁻¹⁶, and the changeover transient (peak current, maximum and minimum torque, speed) agrees with scipy's LSODA solver within 0.3 %.

3.3 Loads and experiments. A centrifugal pump at 80 % (TL∝n2T_L \propto n^2, total J 0.105 kg·m², τm 0.33 s), a large fan (total J 2.245 kg·m², τm 7.15 s) and a constant-torque conveyor at 50 % (total J 0.395 kg·m², τm 1.26 s), in 14 sets of experiments:

SetIndependent variableDependent variables
E1, E7, E13Load type and sizeStar equilibrium speed, t95, t98, coefficient c
E2, E5Timer setting · changeover trigger (timer, current relay, speed)Peak current, time above 3·In, I²t, rotor heat
E3, E11Dead time 5–800 ms · KM3 phase order · switch-on anglePeak current, torque, residual voltage and angle
E4Closed-transition resistor Rt/ZbPeak current, torque, resistor energy
E6, E8Voltage 80–105 % · inertia 0.1–8 kg·m²Run-up time, compared with Kloss and average torque
E9, E10, E12, E14Starting method · running load · supply sizeEnergy, I²t, voltage dip, overload thermal budget, permanent star running

3.4 Proposed timer criterion. tset=max⁡(1.2 t98(Vn), t95(0.9Vn))t_{set} = \max\big(1.2\,t_{98}(V_n),\ t_{95}(0.9V_n)\big): wait until 98 % of the equilibrium speed with a 20 % margin, and never less than the time to 95 % with a 10 % voltage dip.

4. Results

4.1 Timer setting (RQ1)

Measured in τm, the run-up curves of the pump and the fan almost coincide, and making J four times larger does not change t98/τm at all. The result is a coefficient table that applies to motors of any size:

Load (k = torque at rated speed / Tn)nY/nNt98/τmt95/τm at 90 % voltagec
Pump T ∝ n² · k 0.698.2 %1.632.082.1
Pump T ∝ n² · k 0.896.5 %1.892.562.6
Pump T ∝ n² · k 1.094.1 %2.313.443.4
Fan · k 1.094.2 %2.102.942.9
T ∝ n · k 0.896.2 %2.373.964.0
Constant torque · k 0.598.8 %3.10no breakaway3.7
00.250.50.75100.511.522.533.544.5n / n_N00.511.522.500.511.522.533.544.5time t / τmI / Inpump 80 %: n_Y 96.5 % · t98 0.63 s = 1.88 τm0.76·Infan: n_Y 94.2 % · t98 15.01 s = 2.10 τm0.97·Inconveyor 50 %: n_Y 98.8 % · t98 3.89 s = 3.09 τm0.48·In● = 98 % of the equilibrium speed (where Δ should take over)dashed = star equilibrium speed n_Ystar at standstill 2.18·In (= DOL 6.53·In ÷ 3)τm = J·ωs/Tn: pump 0.33 s · fan 7.15 s · conveyor 1.26 s — measured in τm the curves hardly depend on the motor sizeTimer ≈ 1.2·t98 and not shorter than t95 at 90 % voltage (table E13)
Figure 1 · Star-stage run-up of the three loads against time in units of τm

Example: a 37 kW, 1480 rpm pump with a total J of 0.87 kg·m² → Tn=238.8T_n = 238.8 N·m, τm=0.87×157.08/238.8=0.572\tau_m = 0.87 \times 157.08/238.8 = 0.572 s → tset=2.6×0.572≈1.5t_{set} = 2.6 \times 0.572 \approx 1.5 s (set 2–3 s in practice). A 7.5 kW fan with a total J of 2.245 kg·m² → τm=7.15\tau_m = 7.15 s → tset=2.94×7.15≈21t_{set} = 2.94 \times 7.15 \approx 21 s. A blanket “5–10 s for every job” is therefore longer than needed for small pumps and far too short for high-inertia fans. The closed-form Kloss formula popular in textbooks overestimates the time of a double-cage motor by about 74 % (it gives a starting torque of only 0.79·Tn instead of 2.15·Tn), whereas the average-torque method is within 2 %.

4.2 Changeover peak, dead time and phase order (RQ2)

The result that contradicts common belief most is that the 1–3-cycle changeover peak of pumps and fans does not fall with the timer setting. Sweeping the fan timer from 1 to 30 s gives peaks of 7.6–10.4·In, and the pump 7.7–10.5·In, against 8.9·In for DOL. What a correct timer reduces is the time the current stays above 3·In after the changeover: the fan set to 8 s (changeover at 66 % speed) stays above 3·In for 0.96 s, set to 20 s for 0.05 s. A load with low slip in star (conveyor at 50 %) changing over at its equilibrium speed peaks at only 5.6·In.

00.250.50.751051015202530n_sw / n_Nstar equilibrium 94.2 %0369120510152025300123peak I/In (rms)time > 3·In (s)DOL peak 8.90·In · above 3·In for 3.10 schangeover peak (left)high-current time (right)060120180051015202530star timer t_Y (s)% of DOLrotor heatsupply I²ttoo short (< 10 s): long high current · right (15–20 s): I²t ≈ half of DOL · too long: extra rotor heatFan, total J 2.245 kg·m² (τm 7.15 s) · dead time 50 ms · lagging KM3 order
Figure 2 · Timer sweep for the fan: speed at changeover, peak current, high-current time, I²t and rotor heat

The peak is explained by the residual voltage. Pump example (50 ms dead time): before opening n = 1419 rpm, slip 0.054, load torque 37.1 N·m, J = 0.105 → δ=0.848+0.883=1.73\delta = 0.848 + 0.883 = 1.73 rad (99°), half of it from the deceleration of the low-inertia load. The residual voltage is 134 V at −87° to the new delta voltage → ∣ΔV∣=415|\Delta V| = 415 V = 1.04 times DOL → Ipk≈1.36×1.04×6.53=9.2 InI_{pk} \approx 1.36 \times 1.04 \times 6.53 = 9.2\,I_n (simulated 9.7·In). With KM3 in the standard order the angle is −147° → ∣ΔV∣=518|\Delta V| = 518 V → 11.5·In (simulated 11.5·In), and the minimum torque is −4.4·Tn instead of −0.55·Tn.

V_Δ 400 Ve lagging 134 V ∠-87°e standard 134 V ∠-147°Transient driving voltage = |V_Δ − e|DOL: e = 0 → 400 V (reference)lagging order: 415 V = 1.04× DOLstandard order: 517 V = 1.29× DOLsimulated peak: lagging 9.7 · standard 11.5 · DOL 8.9 ×In|ΔV|² = V² + e² − 2·V·e·cos θ (formula E15)To reduce it: large e at small θ →short dead time, lagging order or closed transitionAngles from the new delta winding voltage · counter-clockwise = leading · pump at 80 %, 50 ms dead time
Figure 3 · Phasors of the pump's transient driving voltage |VΔ − e| with KM3 in the lagging and the standard order

The dead time acts in waves (a “phase lottery”). Between 5 and 60 ms, shorter is better (pump: 5.0·In at 10 ms, 6.8·In at 30 ms, 9.7·In at 50 ms) and the lagging order beats the standard order by 10–40 %; beyond that the peak rises and falls with the angle and no value suits every load. Closed transition with Rt = 0.1–0.3·Zb cuts the peak to 2.9–3.8·In (pump) and 5.6–6.7·In (fan), without negative torque.

4.3 Current, energy and heat (RQ3)

Method (fan)Peak currentTimeSupply I²tRotor heat
Direct on line8.9·In3.3 s100 %100 % (30.8 kJ)
Star–delta3.0 → 10.4·In12.7 s51 %130 %
Soft starter 3·In3.0·In16.3 s140 %135 %
VFD1.2·In29.2 s17 %6 %
04080120160% of DOL100100DOLpeak 8.9·In · 3.3 s51130star–delta 12 speak 10.4·In · 12.7 s140135soft starter 3·Inpeak 3.0·In · 16.3 s176VFDpeak 1.2·In · 29.2 ssupply I²trotor heatReduced voltage (Y-Δ, soft start) = high slip for longer → hotter rotor than DOL · a VFD stays at low slipStar–delta halves the supply I²t, but the 1–3-cycle changeover peak is still about as high as DOLpeak = highest rms value · soft starter and VFD computed quasi-statically (no first-cycle transient)
Figure 4 · Supply I²t and rotor heat of each starting method compared with DOL

The electrical energy of one start is at most about a hundred-odd kilojoules (≤ 0.04 kWh in every case of this work), so no starting method saves a meaningful amount of energy. Theory says that without load the rotor heat equals 12Jωs2\tfrac12 J\omega_s^2 whatever the voltage, but with load a lower voltage means slower acceleration and high slip for longer, so the rotor gets hotter than with DOL. The real benefit of star–delta is the lower I²t and sustained voltage dip. On a 250 kVA transformer a 37 kW pump dips the voltage by 4.8 % (DOL), 1.6 % (star stage) and 6.9 % for only 1–2 cycles at the changeover; on a 100 kVA generator set the figures are 32 %, 13.5 % and 41 %.

An additional experiment (E9) found that running permanently in star at light load does save energy: 188 W per 7.5 kW motor at 25 % load, with cos φ improving from 0.46 to 0.79. The break-even point is about 53 %, but the torque margin (Tk,Y/TL ≥ 2.5) limits practical use to about 35–40 % of rating.

020406080100020406080100η, cos φ (%)star torque margin < 2.5×: do not run in starη Δη Ycos φ Δcos φ Y-400-2000200020406080100shaft load (% of 7.5 kW)saving (W)break-even 52.7 %25 %: 188 W · cos φ 0.46 → 0.79Star: 1/√3 winding voltage, less core loss and magnetising current, more slip and copper lossLinear (unsaturated) model · break-even 47–58 % at 95–105 % voltage · in practice keep ≤ 35–40 %
Figure 5 · Efficiency, power factor and power saved running in star versus delta

5. Discussion and case studies

Compared with existing practice. The advice “change over at 85–90 % speed” is right in principle, but electricians cannot measure speed. The c·τm criterion turns this principle into a number from catalogue data (motor J, load J, Pn, nN). The belief that “a longer dead time reduces the surge” is not supported by the experiments, and “a long timer is the safe side” is only partly true: while hanging at the equilibrium speed the fan's winding carries 1.68 times its rated winding current (0.97·In in star against a winding rating of 0.58·In), and a 30 s timer uses 36 % of a class 10 overload's thermal budget per start.

Case studies (simulated cases built from common symptoms; numbers from the model):

  1. Exhaust fan, lights flicker for almost a second — set to 8 s like the pumps; changeover at 66 % speed, above 3·In for 0.96 s → reset to 21 s or use a current relay: 0.05–0.22 s.
  2. Pump trips now and then at the changeover — an rms peak of 9.7–11.5·In falls inside the instantaneous band of a type C MCB → use an MPCB/MCCB with instantaneous trip ≥ 12–13·In, the lagging KM3 order, or closed transition.
  3. Coupling damage after maintenance — KM3 was rewired in the standard order, torque surge −4.4·Tn → wire L1→V2 L2→W2 L3→U2.
  4. Pump on a generator set drops out other contactors — the changeover peak dips the voltage by 41 % → closed transition (≈ 17 %), soft starter (≈ 18 %) or VFD (≈ 9 %).

Limitations. The model has linear magnetics, ideal contactors that open all three phases at once and a zero-impedance supply in the dynamics, and it is extended to other sizes per unit. The results are therefore quantitative trends that should be confirmed by measurement on site.

6. Past, present and future

  • 1889–1891Dolivo-Dobrovolsky (AEG) builds a three-phase squirrel-cage motor and a three-phase system using star and delta connections.
  • early–mid 20th centuryFrom hand-operated star–delta switches to contactors with pneumatic and mechanical timers. Utilities in many countries limit starting currents, so star–delta becomes standard in Europe and Asia.
  • 1970–1990Electronic timers with a fixed dead time, thyristor soft starters and IGBT inverters.
  • TodayIE3/IE4 motors (IEC 60034-30-1) with higher starting currents, AC-3e contactors (IEC 60947-4-1:2018), current-monitoring relays and smart starters. Simulation models like the one in this article can be used to design before installing.
  • Future (projections)Changeover from the motor's state and synchronous closing from residual-voltage measurement; microgrids and battery inverters that make the changeover peak more important; IE4/IE5 motors mostly on VFDs; digital twins for setting up on site.

7. Conclusions and recommendations

  1. Set the timer to tset=c τmt_{set} = c\,\tau_m from the c table (2.1–4.0) and confirm with a clamp meter that the star current has settled before the changeover.
  2. Where the voltage or the load varies, use a current or speed relay instead of a fixed timer (3–4 times shorter high-current time).
  3. Use the shortest dead time the manufacturer approves and wire KM3 in the lagging order L1→V2 L2→W2 L3→U2.
  4. On generator sets or weak supplies consider closed transition, a soft starter or a VFD.
  5. Protective devices must ride through a ~10·In changeover peak, and starts longer than 10 s need a class 20 overload.
  6. For motors running a constant light load below 35–40 %, evaluate permanent star operation to save energy.

Change the timer, the dead time and the phase order yourself in the dynamic simulation lab at Star–delta analysis · lab. Every result in this article can be reproduced with node scripts/yd_research.mjs and python3 scripts/yd_check.py in the site's code repository.

References

  1. IEC 60034-1, Rotating electrical machines — Rating and performance
  2. IEC 60034-12, Starting performance of single-speed three-phase cage induction motors
  3. IEC 60034-30-1, Efficiency classes of line-operated AC motors (IE code)
  4. IEC 60947-4-1, Contactors and motor-starters
  5. IEEE Std 3002.7, Recommended Practice for Conducting Motor-Starting Studies in Industrial and Commercial Power Systems
  6. S. D. Umans, Fitzgerald & Kingsley's Electric Machinery, 7th ed., McGraw-Hill, 2014
  7. P. C. Krause et al., Analysis of Electric Machinery and Drive Systems, 3rd ed., Wiley-IEEE Press, 2013
  8. I. Boldea, S. A. Nasar, The Induction Machine Handbook, CRC Press, 2002

Continue in the library

Frequently asked questions

How many seconds should a star–delta timer be set to?

Calculate the mechanical time constant τm = J·ωs/Tn and multiply it by c ≈ 2–4 depending on the load (centrifugal pump at 80 % ≈ 2.6, fan ≈ 2.9, including a 10 % voltage-dip margin). A 37 kW pump with a total J of 0.87 kg·m² gives about 1.5 s (set 2–3 s), while a 7.5 kW fan with a total J of 2.245 kg·m² gives about 21 s. Then confirm with a clamp meter that the star current has settled before the changeover.

Does a longer timer reduce the current surge at the changeover?

Only the lasting part. The simulated pump and fan give a 1–3-cycle peak of about 7.6–10.5·In whatever the setting (DOL 8.9·In), because the peak is set by the difference between the delta voltage and the residual voltage in the motor. What a correct timer reduces is the time the current stays above 3·In after the changeover, for the fan from 0.96 s (8 s timer) to 0.05 s (20 s timer).

Is a longer dead time between KM2 and KM3 better?

No. The dead time must be long enough for the arc in KM2 to go out before KM3 closes (ready-made timers typically use about 30–80 ms), but lengthening it does not reduce the surge because the angle of the residual voltage keeps rotating. The simulations favour the shortest safe value and the lagging KM3 order L1→V2 L2→W2 L3→U2.

What is star–delta really better at than a direct-on-line start?

It reduces the run-up current to 1/3, the sustained voltage dip to 1/3 and the supply I²t by 25–50 %. It does not save energy, and the rotor gets 30–55 % hotter than with DOL. On a generator set the changeover peak can even dip the voltage more than DOL does.

How can the experiments in this article be reproduced?

Open the dynamic simulation lab on the Star–delta analysis page of the lesson library, or run node scripts/yd_research.mjs and python3 scripts/yd_check.py in the site's code repository, which use the same model as this article.